Description

Complying with HVAC standards and building codes, we produce the Senseair Sunlight CO2 - the most energy-efficient NDIR CO2 sensor in the world. Sunlight can be used in a wide range of applications but is optimal for battery-powered and wireless applications, as well as in places where a reliable and safe sensor with a long service life is required.

The module is designed for easy integration into products. The optical solid-state design with no moving parts makes this sensor durable and vibration-resistant.

Thanks to our automatic baseline correction, Sunlight CO2 requires no maintenance, which means you can install the sensor and forget about it for its entire service life, and it will still remain accurate.

Features

  • Ultra-low power consumption
  • Complies with ANSI/ASHRAE Standard 62.1-2022
  • Complies with RESET grade B standard
  • Complies with WELL Building Standard® (WELL v2™)
  • High accuracy
  • Reliability
  • Mass production
  • Self-correcting
  • Specifications
  • Applications

Specifications

Measured gas Carbon dioxide (CO2)
Operating principle Non-dispersive infrared
Measurement range (CO2) 400 – 5000ppm; extended range up to 10000 ppm
Accuracy (CO2) ±50ppm ±3% of reading 1.2 (extended range ±10% of reading)
Average current 1–30µA
Measurement period Default: once every 16s, 8 samples (configurable)
Peak current < 80mA
Power supply 3.05 – 5.5 V3
Dimensions 34 x 21 x 12mm
Weight 5g
Expected service life >15 years
Operating range 0-50°C, 0-85% RH
Storage temperature -40-70°C
Output signal UART, I2C

Note 1: 15-35°C, 0-80% RH, after 3 ABC (automatic baseline correction) periods
and default measurement settings.
Note 2: Specifications include the error of calibration gas
mixtures (±1%).
Note 3: Not protected against voltage spikes and reverse polarity of the power supply.