Humidity and temperature converter with enhanced relay outputs. — H3060

Available on request
Delivery across Russia
Order phone: +7(800)777-18-50

0 RUB

Description

The converter is equipped with two reinforced relay outputs for signaling, indication, or control of external devices. Each relay has settings for delay, hysteresis, and sound signal enabled. The parameters are easily adjustable using a computer or the keyboard on the sensor's front panel. The converter is controlled by a microprocessor housed in a durable plastic case with connection terminals. A large two-line LCD display is designed to simultaneously show two parameters. If necessary, the display can be turned off.

ATTENTION, the device is currently discontinued.

  • Specifications
  • Overall Drawing
  • Electrical diagram
  • Applications

Sensor

N3060

Output signal

2x Relay

Temperature

Range

-30 to +80°C

Accuracy

±0.4°C

Relative Humidity

(at RH 5-95% and at 23°C)

Range

0 to 100 %RH

Accuracy

±2.5 %RH

Discrete inputs

none

Sensor power supply voltage

110 - 240Vac, 50 - 60 Hz

Maximum switchable voltage, current and power by relay output

250V, 8A, 2000VA/AC

Accuracy and range of dew point temperature measurement

±1.5°C at ambient temp. T<25°C and RH >30%
range -60 to +80 °C

Accuracy and range of absolute humidity measurement

±1.5 g/m3 at ambient temp. <250C, range 0 to 400 g/m3

Accuracy and range of specific humidity measurement

±2.1 g/kg at ambient temp. T < 35°C
range from 0 to 550 g/kg

Accuracy and range of specific enthalpy measurement

±3 kJ/kg at ambient temp. T < 25°C
range from 0 to 995 kJ/kg

Accuracy and range of mixture component ratio measurement

±2.2 g/kg at ambient temp. T < 35°C
range from 0 to 995 g/kg

Sensor / external sensor protection class

IP65/IP40

Sensor operating temperature range

From -30 to +80°C

External sensor operating temperature range

From -30 to +80°C

Operating humidity range (without condensation)

0 to 100 %RH

Storage temperature range

From -30 to +80°C

Recommended calibration interval

1 year

Dimensions / Weight

136 x 213 x 45 mm (W x H x D), rod length 75 mm, / 350 g

Warranty

3 years

 

 

Connecting the relay to the sensor outputs