Humidity and temperature converter with enhanced relay outputs and an external probe designed for measurement in environments with pressure up to 2.5 MPa. — H3061P
Available on request
Delivery across Russia
Order phone: +7(800)777-18-50
Description
The converter is equipped with two reinforced relay outputs for signaling, indication, or control of external devices and an external probe with a cable length of 1, 2, 4 m, designed for measurement in an environment with pressure up to 2.5 MPa. Delay, hysteresis, and sound signal settings are included for each relay. Parameters are easily adjustable using a computer or the keyboard on the sensor's front panel. The converter is controlled by a microprocessor housed in a durable plastic case with connection terminals. A large two-line LCD display is designed for simultaneous display of two parameters. The display can be turned off if necessary.
Recently, temperature and humidity levels have been considered as the most important parameters responsible for indoor climate quality. Especially in buildings and rooms with large gatherings of people, such as conference halls, hospitals, schools, cinemas, theaters, and wellness centers.
With the help of such sensors, engineers, environmental experts, and healthcare specialists can optimize ventilation to create a comfortable and "Healthy" indoor climate.
ATTENTION, the device is currently discontinued.
- Specifications
- Overall Drawing
- Electrical diagram
- Applications
|
Sensor |
N3061R |
|
|
Output signal |
2x Relay |
|
|
Temperature |
Range |
-30 to +105°C |
|
Accuracy |
±0.4°C |
|
|
Relative Humidity (at RH 5-95% and at 23°C) |
Range |
0 to 100 %RH |
|
Accuracy |
±2.5 %RH |
|
|
Discrete inputs |
none |
|
|
Sensor power supply voltage |
110 - 240Vac, 50 - 60 Hz |
|
|
Maximum switchable voltage, current and power by relay output |
250V, 8A, 2000VA/AC |
|
|
Accuracy and range of dew point temperature measurement |
±1.5°C at ambient temp. T<25°C and RH >30% |
|
|
Accuracy and range of absolute humidity measurement |
±1.5 g/m3 at ambient temp. <250C, range 0 to 400 g/m3 |
|
|
Accuracy and range of specific humidity measurement |
±2.1 g/kg at ambient temp. T < 35°C |
|
|
Accuracy and range of specific enthalpy measurement |
±3 kJ/kg at ambient temp. T < 25°C |
|
|
Accuracy and range of mixture component ratio measurement |
±2.2 g/kg at ambient temp. T < 35°C |
|
|
Sensor / external sensor protection class |
IP65/IP40 |
|
|
Sensor operating temperature range |
From -30 to +80°C |
|
|
External sensor operating temperature range |
From -30 to +105°C |
|
|
Operating humidity range (without condensation) |
0 to 100 %RH |
|
|
Operating atmospheric pressure range |
Up to 2.5 MPa |
|
|
Storage temperature range |
From -30 to +80°C |
|
|
Recommended calibration interval |
1 year |
|
|
Dimensions / Weight |
136 x 159 x 45 mm (W x H x D), probe length 150 mm, diameter 18 mm / 450 g |
|
|
Warranty |
3 years |
|


Connecting the relay to the sensor outputs