Temperature and humidity converter with relay outputs, Ethernet interface, discrete inputs, and an external probe designed for measurement in environments with pressure up to 2.5 MPa. — H3531P
Available on request
Delivery across Russia
Order phone: +7(800)777-18-50
Description
The converter is equipped with two relay outputs for signaling, indication, or control of external devices, and an external probe with a cable length of 1, 2, or 4 m, designed for measurement in environments with pressure up to 2.5 MPa. It also has three discrete inputs for connecting external devices such as smoke detectors, motion sensors, etc. Delay settings, hysteresis, and sound signal settings are included for each relay. Parameters are easily adjustable via computer or the keypad on the sensor's front panel. The converter is controlled by a microprocessor housed in a durable plastic case with terminal connections. A large two-line LCD display is designed to simultaneously show two parameters. The display can be turned off if necessary.
Recently, temperature and humidity levels have been considered among the most important parameters responsible for indoor climate quality. Especially in buildings and rooms with large gatherings of people, such as conference halls, hospitals, schools, cinemas, theaters, and wellness centers.
With the help of such sensors, engineers, environmental experts, and healthcare specialists can optimize ventilation to create a comfortable and "Healthy" indoor climate.
ATTENTION, the device is currently discontinued.
- Specifications
- Overall Drawing
- Electrical diagram
- Applications
|
Specifications |
N3531R |
|
|
Output signal |
2x Relay + Ethernet |
|
|
Temperature |
Range |
-30 to +105°C |
|
Accuracy |
±0.4°C |
|
|
Relative humidity (at RH 5-95% and at 23°C) |
Range |
0 to 100 %RH |
|
Accuracy |
±2.5 %RH |
|
|
Discrete inputs |
yes |
|
|
Sensor power supply voltage |
9 - 30 Vdc |
|
|
Maximum switchable voltage, current and power by relay output |
50V, 2A, 60VA |
|
|
Accuracy and range of dew point temperature measurement |
±1.5°C at ambient temp. T<25°C and RH >30% |
|
|
Accuracy and range of absolute humidity measurement |
±1.5 g/m3 at ambient temp. <250C, range 0 to 400 g/m3 |
|
|
Accuracy and range of specific humidity measurement |
±2.1 g/kg at ambient temp. T < 35°C |
|
|
Accuracy and range of specific enthalpy measurement |
±3 kJ/kg at ambient temp. T < 25°C |
|
|
Accuracy and range of mixture component ratio measurement |
±2 g/kg at ambient temp. T < 35°C |
|
|
Sensor / external sensor protection class |
IP40/IP40 |
|
|
Sensor operating temperature range |
From -30 to +80°C |
|
|
External sensor operating temperature range |
From -30 to +105°C |
|
|
Operating humidity range (without condensation) |
0 to 100 %RH |
|
|
Operating atmospheric pressure range |
Up to 2.5 MPa |
|
|
Storage temperature range |
From -30 to +80°C |
|
|
Recommended calibration interval |
1 year |
|
|
Dimensions / Weight |
136 x 159 x 45 mm (W x H x D), probe length 150 mm, diameter 18 mm / 450 g |
|
|
Warranty |
3 years |
|

Connection diagram with power adapter

Discrete inputs are not galvanically isolated, the +U terminals are internally connected to the power supply device (+U terminals provide the same voltage level as the power supply voltage).
Connection diagram with power supply via Ethernet cable using a PoE splitter

Connecting relay to sensor outputs