Sulfur Dioxide Concentration Converter — E2618-SO2
Available on request
Delivery across Russia
Order phone: +7(800)777-18-50
Description
The sulfur dioxide concentration converter E2618-SO2 is a representative of the new line of multifunctional measuring instruments PluraSens®.
The converter can be used in food and paper industry enterprises, water treatment plants, laboratories, etc.
The device is equipped with a fully calibrated latest generation electrochemical sensor with temperature compensation, which ensures high stability and reliability of readings, as well as a long service life of the device.
Two analog outputs and an RS485 interface operating with the Modbus RTU protocol are used to connect the converter to building safety and automation systems.
Advantages
- Accurate and stable measurement
- Wall-mounted or duct version
- Remote probe (optional)
- 2 configurable analog outputs 4-20 mA or 0-10 V
- Digital RS485 Modbus RTU interface
- Display version available
ATTENTION, the device is currently discontinued.
- Specifications
- Overall dimensions drawing
- Connection diagram
- Applications
| Specifications | |
| Calibration | Sulfur Dioxide SO2 |
| Sensor Type | Electrochemical |
| Detection Method | Diffusion |
| Measurement Range |
0...20 ppm |
| Overload Limit |
150 ppm |
| Resolution | <0.1 ppm |
| Signal Update | every second |
| Response Time | < 30 sec |
| Maintenance Interval | 6 months |
| Sensor Lifetime | > 2 years |
| Self-Diagnostics | Full functionality check at startup |
| Warm-up Time | ≤ 1 min |
| Power Supply | 11...30 V DC |
| Power Consumption | < 2 VA |
| Digital Interface | RS485, Modbus RTU protocol |
| Analog Outputs | 2 × 4-20 mA / 0-10 V, configurable |
| Housing | Light gray ABS plastic, protection rating IP65 |
| Dimensions | 82 × 80 × 55 mm |
| Remote Probe | Protection rating IP20, Cable length standard 3.0 m |
| Application Areas | Industrial premises, outdoor use |
| Operating Conditions | -30..+50 °C, 15...90 %RH; Atmospheric pressure ±10%; not for explosive zones; Non-aggressive environment |
| Note. The sensor may show higher sensitivity to nitrogen dioxide, chlorine, ethylene, acetylene. |
|
| Display (optional) | |
| Operating Temperature | 0...+50 °C |
| Display Size | 72 × 36 mm |
| Number of Characters | 3.5 7-segment |
| Character Height | 14 mm |
| Other Features | Backlight |