eSense Slim is used for measuring CO2 concentration indoors. This product is an ultra-compact transmitter designed for mounting on a wall or in a ventilation duct with an IP50 protection rating. A 300 mm long cable, connected to the circuit board, allows placing the sensor in hard-to-reach installation locations.
eSENSE™ – a simple and inexpensive CO2 content transmitter that requires no periodic maintenance and is designed for installation in climate zones and ventilation shafts.
eSENSE™ enables cost savings by reducing energy consumption and also helps create a more favorable indoor environment.
eSENSE™ allows measuring CO2 content in ambient air up to 10000 ppm and transmitting data via an analog output
Advantages
- No maintenance required under standard usage conditions
- Two analog outputs
- Automatic self-diagnosis
- Optimal price for connection to DDCs
- 5-year warranty
- Specifications
- Overall Drawing
- Connection
- Applications
|
Sensor |
eSENSE Slim |
|
Measured gas |
Carbon dioxide CO2 |
|
Measurement range |
0 – 2000 ppm (optional 5000, 10000ppm) |
|
Accuracy |
± 30 ppm ±3% of measured value |
|
Dimensions |
106 mm x 67 mm x 26 mm |
|
Maintenance |
No maintenance required |
|
Service life |
˃ 15 years |
|
Temperature compensation range |
From 0 to 50 °C |
|
Operating humidity range |
From 0 to 95% RH (no condensation) |
|
Power supply |
24 VAC/VDC |
|
Response time (T1/e) |
2 min. |
|
Data transmission |
Uart (Modbus) |
|
Output #1 linear output |
From 0 to 10 V DC (CO2) |
|
Output #2 linear output |
From 2 to 10 V DC (CO2) |

Attention!
The same grounding scheme must be used for the control system and the sensor
|
Output |
Purpose |
Electrical Characteristics |
Comment (Default settings) |
|
+
┴ |
Power (+)
Power Ground (-) |
24 VAC/DC + (±20%), 2W
24 VAC/DC - |
Red
Black |
|
Output (1) |
Analog output 1 (+) |
0 – 10 VDC |
Brown 0 – 2000 ppm |
|
Output (2) |
Analog output 2 (+) |
2.0 – 10.0 VDC |
Not connected |
|
0.9 – 1.6 VDC |
Status = ERROR |
||
|
0 VDC or 0 mA |
Status = NOT READY |