CO2 Concentration Converter with Indicator and Analog Output — eSENSE FAI II
Available on request
Delivery across Russia
Order phone: +7(800)777-18-50
Description
eSENSE™ FAI II is a simple, affordable, state-of-the-art, maintenance-free CO2 concentration converter with an alarm. It is designed for installation in places where CO2 content monitoring is necessary, such as classrooms or offices.
eSENSE™ FAI II measures the CO2 concentration in the surrounding air and alerts with light and sound signals when permissible levels are exceeded.
Application
eSENSE™ FAI II is an optimal solution for climate monitoring. By measuring CO2 content, the user knows exactly when "fresh" air should be supplied to ensure acceptable indoor air quality. The operation of the ventilation system will depend on the actual need. This helps significantly reduce electricity consumption while maintaining a healthy indoor climate. eSENSE™ FAI II is suitable for both European and American standards.
Advantages
- Sound alarm
- Mute button
- Analog output
- Built-in self-diagnosis system
- No maintenance required
- Color indication
3 alarm levels:
Green: 0 - 800 ppm
Yellow: 800 - 1400 ppm
Red: >1400 ppm
- Specifications
- Overall dimensions
- Connection
- Applications
|
Sensor |
eSENSE FAI |
|
Measured gas |
Carbon dioxide CO2 |
|
Measured CO2 range |
0 – 2000 ppm |
|
CO2 measurement accuracy |
± 30 ppm ±3% of the measured value |
|
Maintenance* |
No maintenance required |
|
Service life |
˃ 15 years |
|
Temperature compensation range |
From 0 to 50°C |
|
Operating humidity range |
From 0 to 95% RH (non-condensing) |
|
Power supply |
24 V AC/DC±20%, 50-60Hz |
|
Power consumption |
Average < 1 W |
|
Response time (T1/e) |
< 10 sec at 30 cc/min < 3 min diffusion time |
|
Start-up time |
≤ 1 min. |
|
Data transmission |
UART (Modbus Protocol) |
|
Warranty |
5 years |
|
Output No. 1 |
0 – 10 V DC (CO2) |
*No maintenance required when the ABC self-calibration system is enabled and used under normal conditions.

Attention!
The same grounding scheme must be used for the control system and the sensor.
|
Terminal |
Purpose |
Electrical Characteristics |
Note Default Settings |
Note Settings of this sensor |
|
+ ~
┴ |
Power (+)
Power Ground (-) |
24 VAC/DC + (±20%), 2W
24 VAC/DC - |
|
|
|
Out(1) Out(2) |
Analog output 1 (+) |
0-10 VDC |
0-2000 CO2
|
|
|
Green indicator
|
|
|
|
Lights up when concentration is below 800 ppm
|
|
Yellow indicator
|
|
|
|
Lights up when concentration is from 800 to 1400 ppm
|
|
Red indicator |
|
|
|
Lights up when concentration is 1400 ppm and above |
|
Button |
|
|
|
When pressed, turns off the buzzer for 30 minutes. After 30 minutes, the buzzer will sound again if the CO2 concentration is above 1400 ppm |