CO2 Sensor with Fast Response — CO2 Sensor Engine K30 FR
Available on request
Delivery across Russia
Order phone: +7(800)777-18-50
Description
The sensor on the K30 platform, in the basic CO2 Engine® K30 FR version, is used in a wide range of systems. The platform is designed as an OEM module for embedded control equipment applications and can be adapted to customer requirements. This document describes a specific model of this platform optimized for fast-response CO2 Engine® K30 FR measurements.
CO2 Engine® K30 FR is a high-performance, linear CO2 sensor with a short response time. It is specially designed for equipment where rapid CO2 measurement updates are required. The sample cell is well protected by a particle filter and is designed for fast diffusion without the need for external pumping. Additionally, there is an intake tube for real-time monitoring. Despite the very precise and reliable infrared gas sensing technology, the design is low cost.
The sensor is intended to operate at a stabilized voltage from 4.5 to 14 V, provided that the regulation line and power supply loads remain within ±5%. Under normal operation, the sensor measures CO2 concentration twice per second. The measurement register can be monitored via the I2C bus or UART serial interface. The measured CO2 concentration is processed by a configurable digital filter and is also output to analog linear voltage outputs.
- Specifications
- Printed Circuit Board
- Dimensions
- Applications
|
Specifications |
|
|
Measured gas |
Carbon dioxide CO2 |
|
Measured CO2 range |
0 – 5000 ppm |
|
CO2 measurement accuracy |
± 30 ppm ±3% of measured value |
|
Response time |
2 sec at 0.5 l/min flow, 20 sec - diffusion time |
|
Measurement frequency |
2 Hz |
|
Temperature compensation range |
from 0 to +50 °C |
|
Operating humidity |
from 0 to 95% relative humidity (no condensation) |
|
Storage / operating temperature |
from -30 to +70 °C |
|
Dimensions |
5.1 x 5.7 x 1.4 cm (L x W x H) |
|
Power supply |
from 4.5 to 14.0 VDC value (no reverse polarity protection) stabilized voltage ±5% under load and line variations. Voltage ripple < 100mV. |
|
Power consumption |
< 600 mA peak, 70 mA average |
|
Output to specified accuracy level |
1 min |
|
Service life |
> 3 years |
|
Standards compliance |
RoHS directive 2011/65/EG Tested according; Immunity: EN 61000-6-1:2007, Emission: EN 61000-6-1:2007 |
|
Communication |
UART, Modbus. Connector for direct connection to RS485 receiver. |
|
OUT 1 |
D/A Resolution: 10 mV (10 bit) Linear conversion range: from 0 to 10 V = from 0 to 5,000 ppm Electrical characteristics: ROUT < 100 Ω RLOAD > 5 kΩ |
|
OUT 2 |
D/A Resolution: 5 mV (10 bit) Linear conversion range: from 0 to 5V = from 0 to 5000 ppm Electrical characteristics: ROUT < 100 Ω RLOAD > 5 kΩ |
|
OUT 3 |
Digital (High/Low) output, 700/800 ppm |
|
OUT 4 |
Digital (High/Low) output, 900/1000 ppm |



You may find useful