Electromagnetic Flowmeter for Partially Filled Pipes — IZMERKON EM 370

Available on request
Delivery across Russia
Order phone: +7(800)777-18-50

0 RUB

Description

The electromagnetic flowmeter for partially filled pipes IZMERKON EM 370 consists of a converter, a flow sensor, and a level sensor.

For automatic calculation of the current flow rate and display of accumulated flow, flow velocity, medium level, and other parameters, it is sufficient to enter the pipeline diameter in the flowmeter settings.

The minimum medium level can be 10% of the volume of the medium in the filled pipe. This type of flowmeter is best suited for accounting wastewater, rainwater, as well as for wastewater discharge systems and irrigation systems.

Features

  • The IZMERKON EM 370 flowmeter can measure the flow of liquid in partially filled pipes, making it especially useful for use in irrigation systems;
  • The flowmeter can operate on a solar panel, which is especially convenient for use in remote areas where there is no access to industrial power supply;
  • Thanks to the safe and durable material of construction, the service life of the flowmeter is longer than standard ones. Typically, the flowmeter can be operated for at least 5-10 years or more;
  • The flowmeter can be manufactured with lining, allowing it to be used for measuring the flow of drinking water, groundwater, and other liquids. Many companies supplying drinking water use this type of flowmeter in large diameter pipelines;
  • For measuring the liquid level, the flowmeter design includes an accurate compact ultrasonic level sensor. After measuring the level, the flowmeter records the obtained value and then uses this parameter to calculate the liquid flow. The blind zone of the ultrasonic level sensor is minimal, and its accuracy reaches ±1 mm.
  • Specifications
  • Overall dimensions drawing
  • Applications

Specifications

Pipeline diameter DN 200…DN 3000 (8"-120")
Accuracy ±2.5% of measured value at flow velocity ≥ 0.5 m/s
Flow velocity 0.1…15 m/s
Design Remote (standard cable length 10 m, maximum 30 m)
Conductivity of measured medium > 5 µS/cm, demineralized water > 20 µS/cm
Protection degree Transmitter: IP65
Sensor: IP65 standard, IP68 (available only for remote design)
Electrode material Stainless steel SS316L, Hastelloy C, Hastelloy B, titanium, tantalum, platinum-iridium alloy
Power supply voltage 20…36 V (DC)
Power consumption <20 W
Output signal Analog: 4…20 mA (load 0…750 Ohm)
Frequency: Forward and reverse flow output with frequency range
1...5000 Hz
Alarm: Two isolated open collectors are used
for alarm signal output
Digital interfaces Standard RS485 MODBUS, optional HART, GPRS, PROFIBUS
Display LCD display, 128x128 mm, three lines, 4 buttons
Ambient temperature -20...+60°C
Measured medium temperature -20...+80°C
Lining material PTFE (-20…+150°C, DN 200-DN 1600)
FEP (-20…+120°C, DN 200-DN 1800)
PFA (-20…+160°C, DN 200-DN 800)
Polyurethane (-10…+60°C, DN 200-DN 1600)
Process connection Flanges DIN EN-1092-1 PN10 / PN16 / PN25 / PN40 / PN64 / PN100
JIS 10K / 20K / 30 K
ANSI 150# / 300# / 600#
Sensor material Measuring tube: stainless steel SS304
Flanges and housing: standard carbon steel, optional
stainless steel SS304 / SS316L
Transmitter material Aluminum alloy with epoxy coating
Operating pressure 0.6 MPa standard, optional 150 lb
Information on display Current flow, accumulated flow, flow velocity
Diagnostic functions High and low level alarms, alarm signaling,
empty pipe detection, self-diagnostics
Accumulated flow counter Three built-in totalizers: forward flow, reverse
flow and net flow
Units of measurement L/s, L/m, L/h, m3/s, m3/m, m3/h, UKG, USG, gal/s, gal/m, gal/h, kg/s, kg/m,
kg/h, t/s, t/m, t/h
Menu language English

The specified overall dimensions are for reference only and may vary depending on the design. Exact dimensions must be confirmed when ordering.