Dew Point Sensor for Adsorption Dryers — FA 410

Available on request
Delivery across Russia
Order phone: +7(800)777-18-50

0 RUB

Description

FA 410 Dew Point Sensor – a device for measuring the dew point temperature in compressed air environments. The device can perform measurements even in extremely dry air (down to -80°CTd). The standard application of the sensor is measuring the dew point during deep drying of gases with adsorption dryers. The device can operate at pressures up to 50 bar, and a special version is available that allows measurements at pressures up to 350 bar. A measuring chamber equipped with a quick-release connection is available as an accessory.

With the optional software for the FA410 dew point sensor , it is possible to configure the analog output to display values in % RH, °Ctd, g/m3, mg/m3, ppm V/V.

Features

  • Analog output 4...20 mA
  • High long-term stability values
  • Insensitive to condensation
  • Fast response time
  • Measurement range down to -80...20°Ctd
  • Operating pressure up to 350 bar (special version)

ATTENTION, the device has been discontinued. Modern equivalents are — FA 510, FA 540

  • Specifications
  • Overall Drawing
  • Connection diagram
  • Applications
Technical Specifications FA 410
Measurement Ranges -80...20 °Ctd
-20...50 °Ctd
Accuracy ±1°C at 20...-20°Ctd
±2°C at -20...-50°Ctd
±3°C at -50...-80°Ctd
Operating Pressure -1...50 bar
special version up to 350 bar
Power Supply 24 VDC (16...30 VDC)
Protection Class IP 65
EMC according to DIN EN 61326
Operating Temperature -20...70 °C
Electrical Connection 2 x M12, 5-pin
PC Connection SDI interface
Outputs 4...20 mA = -80...20°Ctd
4...20 mA = -20...50°Ctd
Analog Output Load <500 Ohm
Process Connection G 1/2“
Dimensions Ø 30 mm, length 130 mm
Settings via Software

Units of measurement: % RH, °Ctd, g/m³, mg/m³, ppm V/V;
Scaling of analog output 4...20 mA

Special Version

2-wire circuit 4...20 mA

Contact Number

Contact Color

Designation

Function

Contact 1

brown

SDI

Digital signal

Contact 2

white

-VB

Power supply minus

Contact 3

blue

+VB

Power supply plus 16...30 VDC

Contact 4

black

+I

Positive signal 4...20 mA

Contact 5

 

NC

Not connected

Send request

Request a callback

Information sent successfully

Благодарим за обращение.
Ваша заявка будет рассмотрена в рабочее время:
Пн-Пт с 9 до 18 по московскому времени.